    Elektrotechnik und Medientechnik

    Zeitschriftenartikel

    P. Kummeth, Reinhard Schlosser, P. Massek, H. Schmidt, C. Albrecht, D. Breitfelder, H.-W. Neumüller

    Development and test of a 100 kVA superconducting transformer operated at 77 K

    Superconductor Science and Technology, vol. 13, no. 5, pp. 503-505

    2000

    DOI: 10.1088/0953-2048/13/5/314

    Abstract anzeigen

    High-temperature superconducting (HTS) transformers are very promising candidates for application in electrical power engineering. Their main advantages are reduced size, weight, better efficiency and reduced potential fire and environmental hazards. We have designed, constructed and tested a 100 kVA HTS power transformer operated at 77 K. The nominal primary and secondary currents (voltages) are 18 A (5.6 kV) and 92 A (1.1 kV), respectively. No-load tests, short-circuit tests and load tests proved repeatedly that the transformer has the rated capacity. HTS winding losses of 20.6 W and iron losses of 403 W were measured.